<7. HART-COMMUNICATION>
7- 14
IM 01R01B02-00E-E 12th edition October 01, 2014 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
Device setup
Detailed setup
Congure signal
Total reset
Reset totalizer
Device setup
Detailed setup
Congure signal
Temperature unit
degC / degF Select temperature unit
Device setup
Detailed setup
Congure output
Analog output
Indication, test and adjustment of current output :
Flow AO Read Current output in mA
AO Alm typ Lo current < 3,6mA at error
Hi current > 21.0mA at error
Loop Test Set the analogue output x to 4mA, 20mA or arbitrary current.
Finish with ´End´.
D/A Trim Adjustment of current output at 4mA and 20mA.
Device setup
Detailed setup
Congure output
HART output
HART
®
specic parameter :
Poll Addr Poll Address (Function see above) (Def.: 0)
Num req preams Number of leading FF to HART
®
unit (Def.: 5)
Num resp pream Number of leading FF from HART
®
-unit (Def.:5)
Device setup
Detailed setup
Display selection
Selection of measuring value on display,
Different if manual calibration is activated.
For standard calibration table: Flow / Totalizer / Temperature
For manual calibration table: Percent / Temperature