1-171
IM 04L51B01-01EN
Configuring the GX/GP
1
1.19.5 SettingInternalSwitches
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu System settings > Internal
switchsettings
Web application: Config. tab > System settings > Internalswitchsettings
Hardware configurator: System settings > Internalswitchsettings
Description
Setup Item Selectable Range or Options Default Value
First number 1 to 100 1
Last number 1 to 100 1
First number
Select the first internal switch number that you want to set.
Last number
Select the last internal switch number that you want to set.
Internalswitch
Setup Item Selectable Range or Options Default Value
Type Alarm, Manual Alarm
And/Or
1
AND, OR OR
1 Appears when the type is not set to Alarm.
Type
Set the item to assign to the internal switch.
Options Description
Alarm Assigns the internal switch as an alarm output destination.
Manual Specify this to manually operate with the “OCmdRelay” communication
command.
And/Or
Set the internal switch operation conditions when multiple alarm outputs are assigned to the
switch.
When the channel 1 alarm output and channel 2 alarm output are assigned, And and Or
operations are as shown in the figure below.
When set to AND When set to OR
CH1 alarm
Internal switch
S001
CH2 alarm
On
On
On
1.19ConfiguringSystemSettings(Timezone,displaylanguage,statusrelay,etc.)