14
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation
GS 04L53B01-01EN Nov. 10, 2015-00
PULSE INPUT MODULE
(Model GX90XP)
GX90XP
•
Application:Pulseinput(owsumandthelike)
• Numberofinputs:10
• Measurementinterval:100ms(shortest)
• Input type: Contact (open collector, voltage-free
contact),level(5Vlogic)
• Inputformat:Pulleduptoapprox.5Vthrough5
kΩ,commonpotentialsharedwithinthesame
module
• Inputrange:Upto20kHz*
*30Hzwhenthechatteringlterisinuse(On)
• Minimumdetectionpulsewidth:25μs*
*15mswhenthechatteringlterisinuse(On)
• Measurementaccuracy:Count±1pulse
Forintegrationcomputation*,thefollowing
accuracies are added.
Computationstart:+1scaninterval
Computationstop:−1scaninterval
*Integrationrequiresthemathfunction(/MToption).
• Chatteringlter:Removeschatteringupto5ms
(can be turned on/off on each channel)
*Whenthechatteringlterisoff,connectGX/GP/GMso
that it is not affected by the noise.
• Input threshold level:
Contact (open collector, voltage-free contact):
Countedwhenachangefrom100kΩor
higherto200Ωorlowerisdetected
Level(5Vlogic):
Countedwhenachangefrom1Vorlower
to3Vorhigherisdetected
• Hysteresiswidth:Approx.0.2V
• Contact, transistor rating:
Contact:15VDCorhigherand30mAor
higherrating.Minimumapplicableload
current1mAorless.
Transistor:Withthefollowingratings:Vce>
15VDC,Ic>30mA
• Allowableinputvoltage:±10VDC
• Insulation type: Photocoupler isolation,
transformerisolation
• Terminaltype:M3screwterminalorclamp
terminal
• Withstand voltage:
Betweentheinputterminalsandtheinternal
circuit:1500VACfor1minute
• Insulation resistance:
Betweentheinputterminalsandtheinternal
circuit:20MΩorgreaterat500VDC
Safety and EMC Standards
• SafetyandEMCStandards:Sameasthedigital
inputmodule
Construction
• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20
• Material: Polycarbonate
• Color;
Front:Charcoalgreylight(CC28)
Bezel:Smokeblue(CC53)
• Dimensions:45.1mm(W)x111mm(H)x133.1
mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply
SuppyfromGX/GP,GX60expandableI/O,GM90PS
powersupplymodule.
• Powerconsumption:0.9Worless
Isolation
Pulse input CH1
Pulse input CH2
Pulse input CH3
Pulse input CH4
Pulse input CH5
Pulse input CH6
Pulse input CH7
Pulse input CH8
Pulse input CH9
Pulse input CH10
Functional insulation
Input circuit
Internal circuit
Terminal arrangements
M3 screw terminal/Clamp terminal
No. Symbol No. Symbol
21 CH6 + 11 CH1 +
22 − 12 −
23 CH7 + 13 CH2 +
24 − 14 −
25 CH8 + 15 CH3 +
26 − 16 −
27 CH9 + 17 CH4 +
28 − 18 −
29 CH10 + 19 CH5 +
30 − 20 −
* Negativeterminal(common)potentialshared