6.3.2 Operation when an error occurs
System Alarms
The device has malfunctioned and normal measurement is not possible. The product might need to be
replaced.
NE107
Error messages
Analog
output
Pulse
output
Frequency
output
Status
output
Vortex
frequency
Built-in
temperature
Analog
input
Instantaneous
ow rate
Fluid
temperature
Fluid
pressure
Fluid
density
Fluid
density
ratio
Specic
enthalpy
Flow rate
total
Indicator HART
- -
Burn-out
(HW)
Stop
Open
(HW)
- - - - - - - -
F AL-010 010:CPU failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-011 011:CPU failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-012
012:Main
storage failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-013
013:Sub storage
failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-014
014:Main ASIC
failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-015
015:Sub ASIC
failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-016
016:ADC circuit
failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-017
017:Signal circuit
failure
Burn-out Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-018
018:Power circuit
failure
Burn-out
(L)
Stop Operation
Fixed at
0%
Fixed at
0%
Fixed at
0%
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-020
020:Flow sensor
failure
User
setting
Flow
sensor
alarm
action
Stop Operation
User
setting
Flow
sensor
alarm
action
Operation Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-021
021:Temperature
sensor failure
User
setting
Temp
sensor
alarm
action
Stop Operation Operation
User
setting
Temp
sensor
alarm
action
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
F AL-023
023:Analog input
failure
User
setting
Aux input
alarm
action
Stop Operation Operation Operation
User
setting
Aux input
alarm
action
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Stop
<6. Parameters>
36
IM 01F07A01-01EN

Table of Contents

Other manuals for YOKOGAWA VY Series