Operational limitations
Table 9: Operational limitations
Unit
models
Leaving liquid
temperature °F (°C)
Liquid flow gpm (Lpm) Air on ambient coil °F (°C)
Minimum Maximum Minimum Maximum Minimum Maximum
Cooling, low temperature process chiller
0035PJP 14 (-10) 68 (20) 37 (140) 126 (477) -4 (-20) 118.4 (48)
0070PJP 14 (-10) 68 (20) 74 (280) 252 (954) -4 (-20) 118.4 (48)
0105PJP 14 (-10) 68 (20) 111 (420) 378 (1,431) -4 (-20) 118.4 (48)
0140PJP 14 (-10) 68 (20) 148 (560) 504 (1,904) -4 (-20) 118.4 (48)
0035PJS 14 (-10) 68 (20) 47 (140) 126 (477) -4 (-20) 118.4 (48)
0070PJS 14 (-10) 68 (20) 74 (280) 252 (954) -4 (-20) 118.4 (48)
0105PJS 14 (-10) 68 (20) 111 (420) 378 (1,431) -4 (-20) 118.4 (48)
0140PJS 14 (-10) 68 (20) 148 (560) 504 (1,904) -4 (-20) 118.4 (48)
Cooling, water or glycol
0035PJP 40 (4.4) 68 (20) 37 (140) 126 (477) -4 (-20) 118.4 (48)
0070PJP 40 (4.4) 68 (20) 74 (280) 252 (954) -4 (-20) 118.4 (48)
0105PJP 40 (4.4) 68 (20) 111 (420) 378 (1,431) -4 (-20) 118.4 (48)
0140PJP 40 (4.4) 68 (20) 148 (560) 504 (1,904) -4 (-20) 118.4 (48)
0035PJS 40 (4.4) 68 (20) 37 (140) 126 (477) -4 (-20) 118.4 (48)
0070PJS 40 (4.4) 68 (20) 74 (280) 252 (954) -4 (-20) 118.4 (48)
0105PJS 40 (4.4) 68 (20) 111 (420) 378 (1,431) -4 (-20) 118.4 (48)
0140PJS 40 (4.4) 68 (20) 148 (560) 504 (1,904) -4 (-20) 118.4 (48)
Heating
0035PJP 77 (25) 140 (60) 37 (140) 126 (477) -13 (-25) 109.4 (43)
0070PJP 77 (25) 140 (60) 74 (280) 252 (954) -13 (-25) 109.4 (43)
0105PJP 77 (25) 140 (60) 111 (420) 378 (1,431) -13 (-25) 109.4 (43)
0140PJP 77 (25) 140 (60) 148 (560) 504 (1,904) -13 (-25) 109.4 (43)
0035PJS 77 (25) 140 (60) 37 (140) 142 (537) -13 (-25) 109.4 (43)
0070PJS 77 (25) 140 (60) 74 (280) 284 (1,073) -13 (-25) 109.4 (43)
0105PJS 77 (25) 140 (60) 111 (420) 426 (1,610) -13 (-25) 109.4 (43)
0140PJS 77 (25) 140 (60) 148 (560) 568 (2,147) -13 (-25) 109.4 (43)
Note:
• For water system applications, the liquid flow rate for 0035, 0070, 0105, and 0140 models
must be above 57 gpm (216 Lpm), 114 gpm (431 Lpm), 171 gpm (647 Lpm), and 228 gpm
(863 Lpm), respectively.
• For glycol system applications, if the flow rate for 0035, 0070, 0105, and 0140 models is
potentially less than 57 gpm (216 Lpm), 114 gpm (431 Lpm), 171 gpm (647 Lpm), and 228
gpm (863 Lpm), respectively, select the optional low-flow type flow switch.
YMAE Air-Cooled Inverter Scroll Chiller and Heat Pump80