Refrigerant and oil charge
Table 13: Refrigerant and oil charge, R-454B
YMAE 0035PJP 0070PJP 0105PJP 0140PJP 0035PJS 0070PJS 0105PJS 0140PJS
Sys 1 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
Sys 2 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
Sys 3 - 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
- 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
Sys 4 - 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
- 25.4
(11.5)
25.4
(11.5)
25.4
(11.5)
Sys 5 - - 25.4
(11.5)
25.4
(11.5)
- - 25.4
(11.5)
25.4
(11.5)
Sys 6 - - 25.4
(11.5)
25.4
(11.5)
- - 25.4
(11.5)
25.4
(11.5)
Sys 7 - - - 25.4
(11.5)
- - - 25.4
(11.5)
Refrigerant
charge, lb
(kg)
Sys 8 - - - 25.4
(11.5)
- - - 25.4
(11.5)
Tonnes of CO
2
equivalent (GWP)
10.8 21.7 32.5 43.3 10.8 21.7 32.5 43.3
Sys 1 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
Sys 2 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
Sys 3 - 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
- 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
Sys 4 - 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
- 6.34
(3.0)
6.34
(3.0)
6.34
(3.0)
Sys 5 - - 6.34
(3.0)
6.34
(3.0)
- - 6.34
(3.0)
6.34
(3.0)
Sys 6 - - 6.34
(3.0)
6.34
(3.0)
- - 6.34
(3.0)
6.34
(3.0)
Sys 7 - - - 6.34
(3.0)
- - - 6.34
(3.0)
Oil charge,
gal (L)
Sys 8 - - - 6.34
(3.0)
- - - 6.34
(3.0)
Note:
• Oil type: FVC85EA
• Both systems are charged with additional oil before delivery.
• The oil charge show in this table is the total oil charge amount.
YMAE Air-Cooled Inverter Scroll Chiller and Heat Pump88