Figure 32: Modular array 0070, 0105, and 0140 rigging holes
Callout Component
A Rigging holes located at the ends of unit in the modular array
Note:
- Rigging holes are located at bottom base frame.
- To prevent damage to the unit from the lifting chains, lift the unit using lifting lugs
and a spreader bar or a frame of sufficient width.
Moving the unit by crane
Johnson Controls suggests moving the units using a crane for transit transfer. For 0070, 0105, and
0140 models, do not use a forklift truck.
45YMAE Air-Cooled Inverter Scroll Chiller and Heat Pump