Electrical data
Table 12: Electrical data
With hydro kitMain power supply
(3-phase)
Control supply
(1-phase)
YMAE No. of
modules
Voltage
(V)
Voltage
limits
Voltage
(V)
Voltage
limits
Hz SCCR
(A)
Max
FLA
(A)
MCA
(A)
Min. dual
elem.
fuse/CB
(Min. OP)
(A)
Max.
dual
elem.
fuse/CB
(Max.
OP)
(A)
0035PJS46 1 460 414-506 115 104-127 60 65 84 92 90 110
0070PJS46 2 460 414-506 115 104-127 60 65 151 159 175 175
0105PJS46 3 460 414-506 115 104-127 60 65 262 270 300 300
0140PJS46 4 460 414-506 115 104-127 60 65 328 336 350 350
0035PJP46 1 460 414-506 115 104-127 60 65 75 83 90 110
0070PJP46 2 460 414-506 115 104-127 60 65 142 149 150 175
0105PJP46 3 460 414-506 115 104-127 60 65 230 238 250 250
0140PJP46 4 460 414-506 115 104-127 60 65 296 304 300 300
87YMAE Air-Cooled Inverter Scroll Chiller and Heat Pump