Table 11: Four-pipe physical data, 0035 to 0140, 460 V, 3-phase, 60 Hz
Four-pipe model 0035PJS 0070PJS 0105PJS 0140PJS
Type Braze plate exchanger
Water connection Victaulic
Nominal water flow rate for
cooling
83.97 (317.86) 167.9 (635.57) 251.9 (953.55) 335.9 (1,271.52)
Nominal water flow rate for
heating
90.04 (340.84) 180.1 (681.75) 270.1 (1,022.44) 360.2 (1,363.51)
Cooling
83.90 (317.60) 167.8 (635.19) 251.7 (952.79) 335.6 (1,270.38)
Heating
Nominal water flow rate for
simultaneous heating and
cooling
gpm (Lpm)
109.1 (413.0) 218.2 (825.98) 327.3 (1,238.97) 436.4 (1,651.95)
Pressure drop for cooling 13.4
Pressure drop for heating 15.3
13.4 (cooling)Pressure drop for
simultaneous heating and
cooling
ft H
2
O
22.0 (heating)
Working range leaving
water temperature for
cooling
°F (°C) 14.0 ~ 68.0 (-10 ~ 20)
Working range leaving
water temperature for
heating
°F (°C) 77.0 ~ 140.0 (25 ~ 60)
Cooling: 14.0 ~ 68.0 (-10 ~ 20)
Water
side heat
exchanger
Working range water
leaving temperature for
simultaneous heating and
cooling
°F (°C)
Heating: 77.0 ~ 140.0 (25 ~ 60)
Length, without pump kit in. (mm) 88.2 (2,240) 120.1 (3,051) 192.9 (4,900) 265.8 (6,751)
Width, without pump kit in. (mm) 47.2 (1,199) 88.2 (2,240)
Height, without pump kit in. (mm) 99 (2,515)
Shipping weight without
pump kit
lb (kg) 2,602 (1,180) 5,627 (2,552) 8,564 (3,885) 11,495 (5,214)
Dimensions
and weight
Operation weight without
pump kit
lb (kg) 2,668 (1,210) 5,759 (2,612) 8,762 (3,974) 11,759 (5,334)
Voltage V/Ph/Hz 460/3/60
MCA without pump kit Amps 74 140 206 272
Electrical
features
RLA without pump kit Amps 66 132 198 264
Note:
• Rated cooling performance: chilled EWT/LWT 54°F/44°F (12.2°C/6.7°C), outdoor air 95°F
IPLV data per AHRI standard 550/590 I-P.
• Rated heating performance: hot LWT 105°F (40.6°C), outdoor air 47°F/43°F (8.4°C/6.1°C)
(DB/WB), the water flow rate used is determined by the hot EWT/LWT 95°F/105°F
(35°C/40.6°C).
• Simultaneous heating and cooling: chilled LWT 44°F (6.7°C), water flow rate is determined
by the water temperature at rated cooling capacity; hot EWT/LWT 95°F/105°F (35°C/40.6°C),
the water flow rate is determined by heating capacity and hot water temperature.
YMAE Air-Cooled Inverter Scroll Chiller and Heat Pump86