VCC-X Operator Interface SD
VCC-X SETPOINTS
53
Setpoint Screen #49 - Warm-Up Supply Air
Temperature Setpoint
VCC-X Spts ID:#
Warmup Supply Air
Setpoint: 100.0ºF
Heating will be controlled to this Supply Air Setpoint during Morn-
ing Warm-Up.
Description Minimum Default Maximum
Warm-Up SAT Setpoint 40ºF
(4.44ºC)
100ºF
(37.78ºC)
240ºF
(115.56ºC)
Setpoint Screen #50 - Cool-Down Supply Air
Temperature Setpoint
VCC-X Spts ID:#
Cooldown Supply Air
Setpoint: 55.0ºF
Cooling will be controlled to this Supply Air Setpoint during Cool-
Down.
Description Minimum Default Maximum
Cool-Down SAT Setpoint 30ºF
(-1.11
ºC)
55ºF
(12.78ºC)
80ºF
(26.67ºC)
Setpoint Screen #51 - PREHEAT-X Cool Mode
and Heat Mode Setpoints
VCC-X Spts ID:#
Preheat-X Spts
Cool Mode: 40.0ºF
Heat Mode: 60.0ºF
If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Cooling and the Heating Modes.
Description Minimum Default Maximum
Preheat-X Cool Mode
Setpoint
35.0ºF
(1.66
ºC)
40.0ºF
(4.5ºC)
90.0ºF
(32.2ºC)
Preheat-X Heat Mode
Setpoint
35.0ºF
(1.66
ºC)
60.0ºF
(15.5ºC)
90.0ºF
(32.2ºC)
Setpoint Screen #52 - PREHEAT-X Vent Mode
Setpoint
VCC-X Spts ID:#
Preheat-X Spts
Vent Mode: 50.0ºF
If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Vent Mode.
Description Minimum Default Maximum
Preheat-X Vent Mode
Setpoint
35.0ºF
(1.66ºC)
50.0ºF
(10.0ºC)
90.0ºF
(32.2ºC)
Setpoint Screen #53 - Superheat Setpoint
VCC-X Spts ID:#
Superheat
Setpoint: 15ºF
The Superheat Setpoint is the target Superheat used by the Refriger-
ant Module to correctly drive the EXV valves.
Description Minimum Default Maximum
Superheat Setpoint 1ºF
(-17.2
ºC)
15ºF
(-16.9ºC)
30ºF
(-1.11ºC)
Setpoint Screen #54 - Space Sensor
Calibration - Current and Offset
VCC-X Spts ID:#
Space Sensor Cal
Current: 0.0ºF
Offset.: 0.0ºF
If the Space Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Space Air Temperature
reading. Enter a positive Sensor Calibration value in Line 4 to raise
the Space Temperature Sensor reading or a negative value in Line
4 to lower the Sensor reading.
Description Minimum Default Maximum
Space Sensor
Calibration Offset
-100.0ºF
(-55.5ºC)
0.0ºF
(0ºC)
100.0ºF
(55.5ºC)
VCC-X Setpoint Screens