Installing MX-ONE
Type of cable Product Number Description
TSR 482 0211/20M RJ45 RJ45 straight
TSR 482 0211/200 Compact SM front, LAN A LAN 0
TSR 901
0452/3000
IP telephone LAN cable (100BaseT)
Network
TSR 902
0240/7000
10BaseT RJ45
TSR 903 021/5000
TSR 903 021/12M
AC/DC DC/DC, general
TSR 490 0116/12M
TSR 490
0116/5000
AC/DC DC/DC, UK
TSR 903 0113/1 Battery AC/DC, UK
Power
TSR 491 413/1100 Fan DC/DC Alarm
Note: Consider the needed cabling for network or server redundancy. For
more information, see the description for MX-ONE TELEPHONY
SYSTEM, chapter REDUNDANCY.
2.13 Environmental Requirements
The exchange room must meet the following requirements:
The air shall not contain any dust, smoke, gases or acid fumes
Temperature +5 to +40
o
C (+41 to +104
o
F)
Relative air humidity 20-80%
The relationship between temperature and air humidity shall not cause
condensation
The equipment must not be exposed to direct sunlight
Make sure that the floor withstands the mass of the PBX
For concrete floor, the distributed load is the total mass of equipment in the
room divided by the area of the room
For wooden floor, extra caution must be taken concerning the spot load
of the cabinets
The floor should be covered by an earthed antistatic carpet in order to
reduce the risk of the exchange being exposed to interference caused by
static electricity
If the batteries are to be installed in the exchange room, they must be of a type
which does not produce gases or acid fumes.
If the batteries are to be installed in a room outside the exchange room, the
environmental conditions must comply with the battery suppliers instructions.
18