Use in potentially explosive atmospheres
16 265Gx, 265Ax IM/265Gx/Ax-EN-07
2.3 Use in areas with combustible dust
Installation must be performed in accordance with EN 61241-14:2004.
Transmitters can only be connected using cable glands certified in accordance with Directive
94/9/EC (ATEX) (not included in scope of delivery). The cable gland must conform to IP 67
degree of protection. The smoldering temperature of the dust must be at least 75 K above
the max. surface temperature of the transmitter. The max. surface temperature is 95 °C and
is obtained by adding together the max. ambient temperature (85 °C) and max. self-heating
(10 K).
CAUTION - Risk
When using separating sensors with an anti-stick coating, be aware of the risk of electrostatic
discharge (with consideration given to the medium and transport speed).
2.4 Category 3 for use in "Zone 2"
The transmitter must be connected using a certified cable gland (not included in scope of
delivery). The cable gland must satisfy the requirements of type of protection "increased
safety Ex e" in accordance with Directive 94/9/EC (ATEX). Additionally, the conditions
stipulated in the type-examination certificate for the cable gland must be observed.
WARNING - Risk of explosion!
Opening the cover presents a risk of spark formation and, therefore, explosion.
Opening the housing during operation (with the operating voltage switched on) is not
permitted.