Table 72: FB Name: SF_MutingPar_2Sensor
Name Data Type Initial Value Description, Parameter Values
VAR_INPUT
Activate BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
S_AOPD_In BOOL FALSE Variable.
OSSD signal from AOPD.
FALSE: Protection field interrupted.
TRUE: Protection field not interrupted.
S_MutingSwitch11 BOOL FALSE Variable.
Status of Muting sensor 11.
FALSE: Muting sensor 11 not actuated.
TRUE: Workpiece actuates muting sensor 11.
S_MutingSwitch12 BOOL FALSE Variable.
Status of Muting sensor 12.
FALSE: Muting sensor 12 not actuated.
TRUE: Workpiece actuates muting sensor 12.
S_MutingLamp BOOL FALSE Variable or constant.
Indicates operation of the muting lamp.
FALSE: Muting lamp failure.
TRUE: Muting lamp no failure.
MutingEnable BOOL FALSE Variable or constant.
Command by the control system that enables the
start of the muting function when needed by the
machine cycle. After the start of the muting func-
tion, this signal can be switched off.
FALSE: Muting not enabled
TRUE: Start of Muting function enabled
S_StartReset BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
Reset BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
DiscTimeEntry TIME T#0s Constant 0..4 s;
Max. discrepancy time for S_MutingSwitch11 and
S_MutingSwitch12 entering muting gate
MaxMutingTime TIME T#0s Constant 0..10 min;
Maximum time for complete muting sequence,
timer started when first muting sensor is actuated.
VAR_OUTPUT
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017AC500-S360