Function Block-Specific Error and Status Codes
Table 82: FB-specific error codes
DiagCode State Name State Description and Output Setting
C001 Reset Error 1 Static Reset signal in state 8001.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
C002 Reset Error 2 Static Reset signal in state 8003.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
C010 Control Error Static signal at ProcessControl in state 8010.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
C111 Init Error Simultaneous rising trigger at Reset and ProcessControl in state 8001.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
C211 Lock Error Simultaneous rising trigger at Reset and ProcessControl in state 8003.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Table 83: FB-specific status codes (no error):
DiagCode State Name State Description and Output Setting
0000 Idle The function block is not active (initial state).
Ready = FALSE
S_OutControl = FALSE
Error = FALSE
8001 Init Block activation startup inhibit is active. Reset required.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE