DiagCode State Name State Description and Output Setting
8002 Safe Triggered safety function.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
8003 Lock Safety function startup inhibit is active. Reset required.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
8010 Output Disable Process control is not active.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
8000 Output Enable Process control is active and safety is enabled.
Ready = TRUE
S_OutControl = TRUE
Error = FALSE
4.6.6.18 SF_EDM
Standards Requirements
IEC 60204-1, Ed.
5.0: 2003
Section 9.2.2: Stop function categories; Category 0
EN 954-1: 1996 5.2: Stop function; stop initiated by protective devices shall put the machine in a safe
state
6.2: Specification of categories: Fault detection (of the actuator, e.g. open circuits)
ISO 12100-2:
2003
4.11.4: Restart following power failure/spontaneous restart
EN 954-1: 1996 5.4 Manual reset
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib