Error
class
Compo-
nent or
Inter-
face
Device Module Channel Error Error text Remedy
E2 1 or 9 1 … 4 1 0 43 Internal error For Safety PLC: Check
Safety PLC switch address
setting. Restart Safety PLC.
If this error persists, replace
Safety PLC
E2 1 … 4 255 30 1 48 Overvoltage or
undervoltage
detected
Restart Safety PLC. Check
Safety PLC setting for
power supply error. If this
error persists, replace
Safety PLC.
E2 1 … 4 255 30 1 43 Internal error Contact ABB technical sup-
port. Replace Safety PLC.
E2 1 … 4 255 30 1 40 Wrong firm-
ware version
Update Safety PLC firm-
ware. Restart Safety PLC. If
this error persists, replace
Safety PLC.
E2 1 … 4 255 30 1 28 Boot project
download error
Reload boot project. If this
error persists, replace
Safety PLC.
E2 1 … 4 255 30 1 1 Wrong user
data
Delete user data from
Safety PLC. Restart Safety
PLC and write user data
again.
E2 1 … 4 255 30 1 0 Operation fin-
ished.
Change Safety PLC switch
address setting or remove
SD-Card from non-safety
PLC.
Restart Safety PLC. If this
error persists, replace
Safety PLC.
E2 1 … 4 255 30 1 18 Internal error Contact ABB technical sup-
port. Replace Safety PLC.
E2 1 … 4 255 30 1 12 Flash read
error
Restart Safety PLC. If this
error persists, replace
Safety PLC. Contact ABB
technical support.
E2 1 … 4 255 30 2 18 Internal error Contact ABB technical sup-
port. Replace Safety PLC.
E2 1 … 4 255 30 2 52 Internal error Contact ABB technical sup-
port. Replace Safety PLC.
E2 1 … 4 255 30 2 43 Internal error Contact ABB technical sup-
port. Replace Safety PLC.
AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
30.03.2017 AC500-S 43

Table of Contents