EasyManua.ls Logo

ABB AC500-S - 3.2.2.1 Description of Safety I;O module states

ABB AC500-S
452 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 14: Overview of transitions in Safety I/O modules (except powering off/on and fatal errors)
Transitions
Safety I/O module states defined in Fig. 13 and Fig. 14 are further explained in
Ä
Chapter 3.2.2.1 “Descrip-
tion of Safety I/O module states” on page 60.
3.2.2.1 Description of Safety I/O module states
INIT
Ä
Fig. 15
The hardware is initialized and internal start-up tests of the Safety I/O module are executed. After a suc-
cessful parameterization, the PROFIsafe communication is expected to be initiated by the PROFIsafe F-
Host.
The Safety I/O Module will remain in this state:
n as long as the undervoltage is detected
n if the parameterization failed or pending
n if the PROFIsafe communication is pending
Users have to check that a dedicated qualifier output bit (PROFIsafe diagnostic) for at least one of the chan-
nels in the given Safety I/O module is set to “1” to verify that PROFIsafe F-Devices are initialized.
PROFIsafe status bits in the F-Host for Safety I/O module:
OA_Req_S = 0
FV_activated_S = 1
Device_Fault = 0
Process data bits in the Safety I/O module process image:
PROFIsafe diagnostic bit = 0
Channel process value = 0
Reintegration request bit = 0
AC500-S Safety Modules