4
Application planning
4.1 Processor module and I/O selection
How to select modules for your automation task: In our main
catalog we of
fer a CPU selector
and several comparative tables to find the modules for your application.
Reference documentation for hardware
4.2
Communication within the PLC
The synchronized serial I/O bus is the I/O data bus for the I/O modules connected with the
processor modules or communication interface modules. Through this bus, I/O and diagnosis
data are transferred.
With its fast data transmission, the I/O bus obtains very low reaction times.
Up to 10 I/O terminal units (for one I/O module each) can be added to one terminal base or
to one AC500-eCo processor module. The I/O terminal units and the AC500-eCo I/O modules,
have a bus input at the left side and a bus output at the right side. Thus the length of the I/O bus
increases with the number of attached I/O modules
Ä
Table 1 “Maximum number of I/O devices
which can be connected to the I/O bus” on page 25.
1 I/O bus connection
The connection of the I/O bus is performed automatically by telescoping the modules on the DIN
rail. The I/O
bus provides the following signals:
Supply voltage of 3.3 V DC for feeding the electronic interface components
3 data lines for the synchronized serial data exchange
several control signals
NOTICE!
Except when using hot swap terminal units, the
I/O bus is not designed for
pulling and plugging modules during operation. If a module is pulled or plugged
on a terminal unit that is not hot swap capable while the bus is running, the
following consequences are possible
reset of the station or of the processor module
system lockup
damage of the module
Application planning
Communication within the PLC