ABB AC500 V3 - Dimensioning of the Fuses

ABB AC500 V3
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I
CPU
*) I
Cx
*) I
I/O
bus
*) I
UPx
*) I
LOADx
*)
CPU/communication module part
CPU 0.110 A - - - -
C1 - 0.050 A - - -
C2 - 0.085 A - - -
C3 - 0.050 A - - -
C4 - 0.050 A - - -
I/O module part
Analog1 - - 0.002 A 0.150 A -
Analog2 - - 0.002 A 0.150 A 0.160 A
Analog3 - - 0.002 A 0.100 A 0.080 A
Analog4 - - 0.002 A 0.100 A 0.080 A
Digital1 - - 0.002 A 0.050 A 8.000 A
Digital2 - - 0.002 A 0.050 A 8.000 A
Digital3 - - 0.002 A 0.050 A 8.000 A
S columns 0.110 A 0.235 A 0.014 A 0.650 A 24.320 A
S I
L+
0.4 A S
I
UP
25 A
I
Total
25.4 A
*) All values in this column are exemplary values
4.3.2 Dimensioning of the fuses
T
o be able to select the fuses for the station correctly, both the current consumption and the
inrush currents (melting integral for the series-connected fuse) must be taken into consideration.
Fuse for S
of the
melting
integrals in
A²s
I
L+ A
I
UPx A
Recommended fuse
Type Value
F1 CPU logic 1.000 » 0.4 - Quick 10 A
F2 Module Dig-
ital1
0.005 - 8.050 Quick 10 A
F3 Module Dig-
ital2
0.008 - 8.050 Quick 10 A
F4 Module Dig-
ital3
0.007 - 8.050 Quick 10 A
F5 Modules
Analog1 +
Analog2 +
Analog3 +
Analog4
0.130 - 0.820 Quick 10 A
Application planning
Power supply dimensioning > Dimensioning of the fuses
2023/03/033ADR011074, 1, en_US28