Use the mains socket which is located inside the control cabinet.
Ä
Chapter 5.1 “Control cabinet assembly for AC500 (Standard)” on page 30
6.2.5 Reference potential
Provide a uniform reference potential in the entire installation and ground all electrical
appliances if possible.
Route your grounding conductors in a star configuration so that no ground loops can occur.
6.2.6 Equipotential bonding
The Installation of equipotential bondings are necessary if there are present or expected poten-
tial dif
ferences between parts of your application.
The impedance of equipotential bonding must be equal or lower than 10 %
of the shield impedance of the shielded signal cables between the same
points.
The conductor cross section of a equipotential bonding must be 16 mm² to
withstand the maximum possible compensating current.
Equipotential bondings and shielded signal cables should be laid close to
each other
.
Equipotential bondings must be connected to PE with low impedance.
For supplying
the PC
Wiring
EMC-conforming assembly and construction > Equipotential bonding