The index of the module is in the right corner of the label.
NOTICE!
Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from
the terminal unit in a powered system.
NOTICE!
Risk of damage to I/O
modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Device Min. required device index for I/O module as of
FW Version 3.0.14
AC522(-XC) F0
AI523 (-XC) D2
AI531 D4
AI531-XC D2
AI561 B2
AI562 B2
AI563 B3
AO523 (-XC) D2
AO561 B2
AX521 (-XC) D2
AX522 (-XC) D2
AX561 B2
CD522 (-XC) D1
DA501 (-XC) D2
DA502 (-XC) F0
DC522 (-XC) D2
DC523 (-XC) D2
DC532 (-XC) D2
DC562 A2
DI524 (-XC) D2
DI561 B2
DI562 B2
DI571 B2
DI572 A1
Maintenance
Replace an I/O module with hot swap > Preconditions for using hot swap