G1 Introduction to AC500 1-123 AC500 / Issued: 07.2006
Needed products
Quantity Product description Order number
1 CPU 07 KT 97/98 with PROFIBUS DP
here: 07 KT 97 with Ethernet and PROFIBUS DP
coupler
GJR5 2530 00 R0272
1 Programming cable 07 SK 90 GJR5 2502 00 R0001
1 PDA11-FBP.050 adapter for FBP, power supply and
field bus
1SAJ 9240 09 R0005
1 PDP22-FBP.050 PROFIBUS DP-V0/V1-FBP 0.5 m,
modular (field bus plug)
1SAJ 2401 00 R1005
1 PDR11-FBP.150 terminating resistor 1SAJ 9240 07 R0001
1 DC505-FBP with 8DI/8DC 1SAP 2200 00 R0001
1 DC532 with 16DI/16DC 1SAP 2401 00 R0001
1 AX522 with 8AI/8AO 1SAP 2500 00 R0001
1 TU506 FBP terminal unit for FBP interface 1SAP 2100 00 R0001
2 TU516 I/O terminal unit for I/O modules 1SAP 2120 00 R0001
1 GSD file for FBP modules ABB_091F.GSD
1 Programming software 907 AC 1131 GJP5 2070 00 R0102
Before starting:
Use the previous installation instructions to assemble and mount the system, also refer to the
dedicated User's manual of the PROFIBUS DP FBP and AC31 series 90 PLC.
Make the wiring and provide power supply to the system (process supply) and to the FieldBusPlug
(use dedicated accessory, e.g. PDA11-FBP.050 which allows to connect a PROFIBUS DP master
with a 9-pin D-Sub and provide power supply for the FBP through an M12 connector).
Set the slave address of the FBP to 1 with the front rotary switches of the S500-FBP module (see
Getting Started with S500-FBP, "Setting the FBP slave address").
Install the AC1131 programming software for AC31 PLCs
If you want to configure the fieldbus using the fieldbus configurator software 907 FB 1131, install this
software. As an alternative, you can also use the fieldbus configurator included in the programming
software.
If you want to use the fieldbus configurator 907 AC 1131 for configuration, copy the PROFIBUS GSD
file ABB_091F.GSD to the folder \Program Files\AC1131\FB1131\Fieldbus\PROFIBUS\GSD. If you
want to configure the fieldbus using the fieldbus configurator included in the programming software,
copy the GSD file to the folder \Program Files\AC1131\Library\PLCConf.
Connect the PC (COM1) to the AC31 CPU (COM1) using the programming cable 07 SK 90.
Connect the CPU to the DC505-FBP module via the FieldBusPlug.
Switch on voltage.
Perform the steps given in the following instructions.