EasyManua.ls Logo

ABB ACH180-04S - Connecting the Power Cables - IEC (Shielded Cables); Connection Diagram

ABB ACH180-04S
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting the power cables – IEC (shielded cables)
■
Connection diagram
PE
PE
L1 L2 L3
R-
R+
UDC+
UDC-
U1 W1
M
PE
3
T1/
U
T2/
V
T3/
W
V1
2
3
4
5
6
7
8
9
8
L1 L2 L3
(L) (N)
1
Drive1
Disconnecting device2
Input power cable3
Two protective earth (ground) conductors. Drive safety standard IEC/EN 61800-5-1
requires two PE conductors for a fixed connection, if the cross-section of grounding
conductor is less than 10 mm
2
Cu or 16 mm
2
Al. For example, you can use the cable
shield in addition to the fourth conductor.
4
Separate PE cable (line side). Use a separate grounding cable or a cable with a separate
PE conductor for the line side, if the conductivity of the fourth conductor or shield
does not meet the requirements for the PE conductor.
5
Motor cable. ABB recommends to use a symmetrical shielded cable (VFD cable) as
motor cable.
6
Separate PE cable (motor side). Use a separate grounding cable for the motor side, if
the conductivity of the shield is not sufficient, or if there is no symmetrically constructed
PE conductor in the cable.
7
360° grounding of the cable shield. Required for the motor cable and brake resistor
cable (if used).
8
Brake resistor (optional, for frames R2...R4 only).9
Electrical installation 67

Table of Contents