Make sure that …
The supply voltage matches the nominal input voltage of the drive. See the type designation
label.
The insulation resistance of the input power cable, motor cable and motor is measured
according to local regulations.
The drive is attached securely on an even, vertical and non-flammable wall.
The cooling air flows freely in and out of the drive.
If the drive is connected to a network other than a symmetrically grounded TN-S system:
You have done all the required modifications (for example, you may need to disconnect
the EMC filter or ground-to-phase varistor). See the electrical installation instructions.
Appropriate AC fuses and main disconnector are installed.
There is an adequately sized protective earth (ground) conductor(s) between the drive
and the switchboard, the conductor is connected to correct terminal, and the terminal is
tightened to the correct torque.
Proper grounding has also been measured according to the regulations.
The input power cable is connected to the correct terminals, the phase order is correct,
and the terminals are tightened to the correct torque.
There is an adequately sized protective earth (ground) conductor between the motor and
the drive, and the conductor is connected to the correct terminal, and the terminal is
tightened to the correct torque.
Proper grounding has also been measured according to the regulations.
The motor cable is connected to the correct terminals, the phase order is correct, and the
terminals are tightened to the correct torque.
The motor cable is routed away from other cables.
No power factor compensation capacitors are connected to the motor cable.
If an external brake resistor is connected to the drive: There is an adequately sized pro-
tective earth (ground) conductor between the brake resistor and the drive, and the con-
ductor is connected to the correct terminal, and the terminals are tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
If an external brake resistor is connected to the drive: The brake resistor is connected to
the correct terminals, and the terminals are tightened to the correct torque.
If an external brake resistor is connected to the drive: The brake resistor cable is routed
away from other cables.
The control cables are connected to the correct terminals, and the terminals are tightened
to the correct torque.
112 Installation checklist of the drive