EasyManua.ls Logo

ABB ACH480 Series - Motor Cable Length; Operational Functionality and Motor Cable Length; EMC Compatibility and Motor Cable Length

ABB ACH480 Series
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Motor cable length
Operational functionality and motor cable length
The drive is designed to operate with optimum performance with the following maximum
motor cable lengths. The values are valid for 4 kHz switching frequency.
Maximum motor cable lengthFrame
ftm
Standard drive, without external options
492150R1, R2
492150R3, R4
With external output chokes
820250R1…R3
656200R4
Note: In multimotor systems, the calculated sum of all motor cable lengths must not
exceed the maximum motor cable length given in the table.
EMC compatibility and motor cable length
To comply with the EMC limits in the European EMC Directive (standard IEC/EN
61800-3), do not exceed these maximum motor cable lengths. They are valid for 4 kHz
switching frequency.
Maximum motor cable length, 4 kHzFrame
C3C2
C1
1)
ftmftmftm
With internal EMC filter
3-phase 380 480 V
100303310--R1
66203310--R2
100303310--R3
100303310--R4
With optional external EMC filter
3-phase 380 480 V
164501645010030R1
164501645010030R2
164501645010030R3
164501003010030R4
1)
Category C1 with conducted emissions only. Radiated emissions are not compatible when measured with
the standard emission measurement setup and must be measured on cabinet and machine installations for
each case.