EasyManua.ls Logo

ABB ACH480 Series - NPN Configuration for Digital Inputs; Connection for Obtaining 0

ABB ACH480 Series
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NPN configuration for digital inputs
Internal and external +24 V power supply connections for NPN (sink) configuration are
shown in the figure below.
External +24 V power supplyInternal +24 V power supply
0 V DC
+24 V DC
DI1
DI2
DI3
DI4
DI5
DI6
+24 V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
+24 V
DGND
DCOM
Connection for obtaining 0 10 V from analog output 2 (AO2)
To obtain 0 10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between AO2 and AGND. Examples are shown in the figure below.
AO2
AGND
500 ohm
0…10 V
AO2
AGND
1 kohm
0…10 V
1 kohm
Analog output 2. Default output 0 20 mA.AO2
Analog common ground.AGND
Electrical installation IEC 77