FusesDrive in-
put cur-
rent
UL (NEC)
type
ACH480-
04-…
Max. fuse rating
for group install-
ation
1)
Type
Bussmann/
Edison type
Voltage
rating
Nomin-
al cur-
rent
AVAA
100UL class TJJS/TJS806008050.0034A-4
100UL class TJJS/TJS10060010060.0042A-4
1)
Branch circuit short-circuit protection for group installation by fuses: Suitable for motor group installation on
a circuit that is capable of delivering no more than 65000 rms symmetrical amperes, 480 V maximum, when
protected by class T fuses.
The same fuse size is specified for several consecutive drive types. This is possible since the physical structure
of the drive types is identical.
UL (NEC) fuse alternatives
UL 248-15 Class T Fast Acting FusesFuseDrive
input
current
UL (NEC)
type
ACH480-04-
EdisonMersen /
Ferraz
Shawmut
LittelfuseBussmann
Voltage
rating
Max.
current
VAA
3-phase U
N
= 480 V
TJS6A6T6JLLS006JJS-660064.202A1-4
TJS6A6T6JLLS006JJS-660065.303A0-4
TJS10A6T10JLLS010JJS-10600106.403A5-4
TJS10A6T10JLLS010JJS-10600109.004A8-4
TJS20A6T20JLLS020JJS-206002011.506A0-4
TJS20A6T20JLLS020JJS-206002015.007A6-4
TJS25A6T25JLLS025JJS-256002520.2011A-4
TJS35A6T35JLLS035JJS-356003527.2014A-4
TJS40A6T40JLLS040JJS-406004040.0021A-4
TJS60A6T60JLLS060JJS-606006045.0027A-4
TJS80A6T80JLLS080JJS-806008050.0034A-4
TJS100A6T100JLLS100JJS-10060010060.0042A-4
UL 248-8 Fast Acting Class J FusesFuseDrive
input
current
UL (NEC)
type
ACH480-04-
EdisonMersen /
Ferraz
Shawmut
LittelfuseBussmann
Voltage
rating
Max.
current
VAA
3-phase U
N
= 480 V
JFL6A4J6JLS6JKS-660064.202A1-4
JFL6A4J6JLS6JKS-660065.303A0-4
JFL10A4J10JLS10JKS-10600106.403A5-4
JFL10A4J10JLS10JKS-10600109.004A8-4
132 Technical data