Parameters 111
D2D The start and stop commands are taken from another drive
through the D2D (Drive-to-drive) Control Word.
4
In1F In2R The source selected by 10.05 Ext2 start in1 is the forward
start signal, the source selected by 10.06 Ext2 start in2 is the
reverse start signal.
5
In1St In2Dir The source selected by 10.05 Ext2 start in1 is the start signal
(0 = stop, 1 = start), the source selected by 10.06 Ext2 start
in2 is the direction signal (0 = forward, 1 = reverse).
6
10.05 Ext2 start in1 Selects source 1 of start and stop commands for external
control location EXT2. See parameter 10.04 Ext2 start func,
selections In1 and 3-wire.
Note: This parameter cannot be changed while the drive is
running.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI6 Digital input DI6 (as indicated by 02.01 DI status, bit 5). 1074070017
DIO4 Digital input/output DIO4 (as indicated by 02.03 DIO status,
bit 3).
1073938947
Timed func Bit 4 of parameter 06.14 Timed func stat. The bit is on when
any one of the four timers configured in parameter group 36
Timed functions is on.
1074005518
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
10.06 Ext2 start in2 Selects source 2 of start and stop commands for external
control location EXT2. See parameter 10.04 Ext2 start func,
selection 3-wire.
Note: This parameter cannot be changed while the drive is
running.
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
DIO5 Digital input/output DIO5 (as indicated by 02.03 DIO status,
bit 4).
1074004483
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
No. Name/Value Description FbEq
State of source 1
(via par. 10.05)
State of source 2
(via par. 10.06)
Command
00Stop
1 0 Start forward
0 1 Start reverse
11Stop