138 Parameters
14.62 Freq out max src When 14.10 DIO3 conf is set to Freq output, defines the real
value of the signal (selected by parameter 14.61 Freq out src)
that corresponds to the maximum DIO3 frequency output
value (defined by parameter 14.64 Freq out max sca).
0 … 32768 Real signal value corresponding to maximum DIO3 output
frequency.
1 = 1
14.63 Freq out min src When 14.10 DIO3 conf is set to Freq output, defines the real
value of the signal (selected by parameter 14.61 Freq out src)
that corresponds to the minimum DIO3 frequency output
value (defined by parameter 14.65 Freq out min sca).
0 … 32768 Real signal value corresponding to minimum DIO3 output
frequency.
1 = 1
14.64 Freq out max sca When 14.10 DIO3 conf is set to Freq output, defines the
maximum DIO3 output frequency.
3 … 32768 Hz Maximum DIO3 output frequency. 1 = 1 Hz
14.65 Freq out min sca When 14.10 DIO3 conf is set to Freq output, defines the
minimum DIO3 output frequency.
3 … 32768 Hz Minimum DIO3 output frequency. 1 = 1 Hz
14.67 RO6 src Selects a drive signal to be connected to relay output RO6.
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
14.70 RO7 src Selects a drive signal to be connected to relay output RO7.
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
No. Name/Value Description FbEq
f
DIO3
(Hz)
14.64
14.65
14.62 14.63
14.6214.63
14.64
14.65
Signal (real)
selected by
par. 14.61
f
DIO3
(Hz)
Signal (real)
selected by
par. 14.61