Section-10
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202 Page 9/19 ABB
Printed in Switzerland – Modifications reserved
10.5.2 GRAPH: Output Power in KW and KVA VERSUS cosphi
DPA 50 Output Power versus cosphi
32
36
38
40
40
404040
40
40
31
505050
50
47.1
44.4
42.1
40
42.1
44.4
36.5
0
10
20
30
40
50
60
-0.85 -0.90 -0.95 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.60
Cosphi
Output Power kW
0
10
20
30
40
50
60
Output Power kV
kW kVA
Fig. AC-AC Efficiency of DPA 50 Module
cosφ
MX Module Range
DPA30 S2 DPA40 S2 DPA50 S2
kW kVA kW kVA kW kVA
Cap.
0.85 18.5 21.8 24.6 29 31 36.5
0.90 24 26.7 32 35.6 40 44.4
0.95 24 25.3 32 33.7 40 42.1
-------
1.00 24 24 32 32 40 40
Ind.
0.95 24 25.3 32 33.7 40 42.1
0.90 24 26.7 32 35.6 40 44.4
0.85 24 28.2 32 37.6 40 47.1
0.80 24 30 32 40 40 50
0.75 22.9 30 30.5 40 38 50
0.70 21.7 30 28.9 40 36 50
0.60 19 30 25.4 40 32 50
Changes of this table without notice – modifications reserved