Section-10
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202 Page 16/19 ABB
Printed in Switzerland – Modifications reserved
10.11 INSTALLATION PLANNING
Clearances X Y
Minimum 200mm 900 mm
UPS Frame type
(50kVA up to 250 kVA)
CLASSIC DPA-50 TRIPLE DPA-150 UPGRADE DPA-250
Dimensions (WxHxD) mm 730x1650x800 730x1975x780 730x1975x800
Battery Cabinet Type
NA
CBAT DPA-120 CBAT DPA-200
Dimensions (WxHxD) mm NA 730x1975x800 1200x1975x800
Accessibility
Totally front accessibility for service and maintenance (no need for
side, top or rear access)
Positioning Min. 20 cm rear space (required for fan)
Input and Output Power Cabling From the bottom on the front
10.11.1 HEAT DISSIPATION PER MODULE WITH NON-LINEAR LOAD
Module size MX
Module Type DPA 30 S2 DPA 40 S2 DPA 50 S2
Heat Dissipation with 100% Non-linear
Load per Module (EN 62040-1-1:2003)
W
1532 2043 2553
Heat Dissipation with 100% Non-linear
Load per Module (EN 62040-1-1:2003)
BTU
5227 6969 8712
Airflow (25° - 30°C) with Non-linear Load
per Module (EN 62040-1-1:2003)
m
3
/h 380 380 380
UPS
Frames
X
Battery
Cabinet
UPS
Frames
X
Figure 1: UPS space recommendation
Figure 2 : : UPS + Battery space recommendation
O
p
en Doors
Y
Open
Doors
Y