Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202 Page 4/16 ABB
Printed in Switzerland – Modifications reserved
2.1.3.2 Dual feed input (Optional Version)
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Frame
type
Load
kVA
cosphi
0.8
Input 3x400V Bypass 3x400V
Output 3x400V
cosphi 0.8
Battery
Fuse B
(Agl/CB)
Cable B (mm
2
)
(IEC 60950-1)
Max. Input
Current
with battery
charging
(A)
Fuse C
(Agl/CB)
Cable
C
(mm
2
)
(IEC
60950-1)
Cable
D
(mm
2
)
(IEC
60950-1)
I nom
Fuse E
+/N/-
(Agl/CB)
Cable E (mm
2
)
for CBAT DPA 120 or
200 ONLY
+ / N / -
Com.
Battery
Sep.
Battery
MX Frames (Frames shall be cabled to there full rating capability)
CLASSIC
DPA 50
50 3x100A 5x25 67 3x100A 4x25 5x25 72 A 3x100A*1 3x25 3x25
TRIPLE DPA-
150
150 3x250A 5x120 or 5x(2x50) 202 3x250A
4x120 or
4x(2x50)
5x120 or
5x(2x50)
218 A 3x300A*1 3x150
3x
(3x25)
UPGRADE
DPA-250
250 3x400A 5x(2x95) 337 3x400A 4x(2x95) 5x(2x95) 362 A 3x500A*1 3x(2x150)
5x
(3x25)
*1 only valid for common battery use
VERSION (DUAL FEED INPUT)
MAINS 3x400/230V
Maintenance Bypass IA1
Cable D
Load 3x400/230V
UPS module 1
F1 F2
Static Switch
IA2-1
Inverter
Rectifier
UPS module 2…4
F1 F2
Static Switch
IA2-2..4
Inverter
Rectifier
UPS module 5
F1 F2
Static Switch
IA2-5
Inverter Module
Rectifier
Frame
Fuse B
Cable B
Fuse C