Section-10
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202 Page 14/19 ABB
Printed in Switzerland – Modifications reserved
10.9.2 BATTERY CABINETS
S-type = For Separate. Battery
C-type = For Common. Battery
CBAT-DPA-120
S-type or C-type
CBAT-DPA-200
S-type or C-type
BATTERY FRAMES
Configuration accommodates:
Max.
120 Batt. block x 24Ah/28Ah
on 8 shelf
3x5=15 blocks/shelf
200 Batt. blocks x 24Ah/28Ah
on 7 shelf
6x5=30 blocks/shelf
Battery fuses / Max. Batt. Strings :
Terminals :
S-type
3 / 3
(Terminal 9 x 16/25mm2)
5 / 5
(Terminal 15 x 16/25mm2)
Battery fuses / Max. Batt. Strings
Terminals :
C-type
3 / 3
+ Com. Connection Bar
3 x (2xM8) +PE 2xM8
5 / 5
+ Com. Connection Bar
3 x (2xM10) +PE 2xM10
Fuse Type (Very Fast acting)
A 3x100 A 5x100A
Dimensions (WxHxD)
mm 730x1975x800 1200x1975x800
Weight with trays and w/o batteries
kg 290 410
Possible Battery configurations
within the Battery Cabinets
Battery Configurations
30x28Ah
40x28Ah
50x28Ah
(2x30)x28Ah
(2x40)x28Ah
(2x50)x28Ah
(3x30)x28Ah
(3x40)x28Ah
Battery Configurations
(2x40)x28Ah
(3x40)x28Ah
(4x40)x28Ah
(5x40)x28Ah
(2x50)x28Ah
(3x50)x28Ah
(4x50)x28Ah
(5x30)x28Ah