10.6 ENVIRONMENTAL CHARACTERISTICS
Module Range MX
Module Type
DPA 30 S2
DPA 40 S2
DPA 50 S2
Audible Noise
with 100% / 50% Load
dBA 64/55 65/56 65/56
Operation temperature °C 0 – 40
Ambient Temperature for
Batteries (recommended)
°C 20 – 25
Storage Temperature °C -25 – +70
Battery Storage Time at Ambient
Temperature
Max. 6 months
Max. altitude (above sea level) m 1000m (3300ft) without de-rating
De-rating factor for use at
altitudes above 1000m sea level
according
( IEC 62040-3)
Meter above sea level (m / ft) De-Rating Factor for Power
1500 / 4850 0.95
2000 / 6600 0.91
2500 / 8250 0.86
3000 / 9900 0.82
Relative Air-humidity Max. 95% (non-condensing)
Accessibility
Totally front accessibility for service and maintenance
(no need for side, top or rear access)
Positioning Min. 20 cm rear space (required for fan)
Input and Output Power Cabling From the bottom on the front
Efficiency AC-AC up to (at cosphi 1.0)
(depending on Module power)
%
Load : 100% 75% 50% 25%
DPA 30-50: 95.2% 95.5% 95.5% 94.5%
Efficiency Non-linear Load
(EN 62040-1-1:2003)
Typically up to 1 % lower of above values
Eco-Mode efficiency at 100% load % 98%
10.7 STANDARDS
Safety
Product Standards Standards
IEC/EN 62040-1 IEC/EN 60950-1
Electromagnetic
Compatibility
Product Standards Standards
IEC/EN 62040-2
IEC/EN 61000-6-2 ; IEC/EN 61000-6-4
IEC/EN 61000-4-2 ; IEC/EN 61000-4-3
IEC/EN 61000-4-4 ; IEC/EN 61000-4-5
IEC/EN 61000-4-6
EMC Classification DPA-30 DPA-40 DPA-50
Emission Class C2 C2 C2
Immunity Class C3 C3 C3
Performance IEC/EN 62040-3
Product certification CE
Degree of protection IP 20