Section-1
04-3008_S1_ABB_OPMCPDPA-S2_GB_121202 Page 19/22 ABB
Printed in Switzerland – Modifications reserved
1.6.1.2 Single Input Feed
To achieve correct Input Cabling see Drawing Section 2, chapter 2.1.2
For single input feed connect the mains input cable to UPS Terminal Block according to the following table:
MAINS INPUT CABLE UPS TERMINAL
Phase L1 1L1
Phase L2 1L2
Phase L3 1L3
NEUTRAL 1N
EARTH PE
For minimum recommended Input Cable Sections and Fuse Ratings Section 2, chapter 2.1.2
Under the connection terminal of the UPS there is a cable-fixing rail to ensure that the cables have been fastened
properly.
1.6.1.3 Dual Input Feed
To achieve correct input cabling see Terminal Block in Section 2, chapter 2.1.2
NOTE: The UPS is supplied (as standard version) with facilities for a single cable feed (for rectifier and bypass).
If dual feed is required unscrew the terminal bridges between
UPS TERMINAL
Rectifier
UPS TERMINAL
Bypass
1L1 2L1
1L2 2L2
1L3 2L3
1N 2N
PE PE
For dual input feed connect the mains input cables to UPS Terminal according to following tables:
MAINS INPUT CABLE UPS TERMINAL
Rectifier
BYPASS INPUT CABLE UPS TERMINAL
Bypass
Phase L1 1L1 Phase L1 2L1
Phase L2 1L2 Phase L2 2L2
Phase L3 1L3 Phase L3 2L3
NEUTRAL 1N NEUTRAL 2N
EARTH PE EARTH PE
For minimum recommended Input Cable Sections and Fuse Ratings Section 2, chapter 2.1.2
Under the connection terminal of the UPS there is a cable-fixing rail to ensure that the cables have been fastened
properly.
1.6.1.4 Preparation for the Output Cabling
Before you start connecting the loads, ensure that the sum of the indicated UPS-module rated powers (OUTPUT
POWER) on the nameplates (on the front side of the UPS-modules) is equal to or larger than the total load
requirements.
The output of the UPS must be fitted with circuit breakers or other kind of protection. These circuit breakers will be
connected between the loads and the UPS and will provide additional protection to the UPS in the event of
overloads and short circuits.
These circuit breakers will enable the protection of each load separately.
The size of the circuit breakers depends on the load rating of the load sockets.
The circuit breakers must comply with the prescribed IEC Standards. It is recommended to provide a separate
output distribution board for the load.