Section-10
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202 Page 5/19 ABB
Printed in Switzerland – Modifications reserved
10.2.2 POWER SELECTION TABLE CONCEPTPOWER DPA MODULES
Concept Power DPA: Power Modules DPA 30 - DPA 50
40
32
24
40
32
24
50
40
30
0
5
10
15
20
25
30
35
40
45
50
DPA 30 S2 DPA 40 S2 DPA 50 S2 DPA 30 S2 DPA 40 S2 DPA 50 S2
MX Module
Output Power kW
0
5
10
15
20
25
30
35
40
45
50
Output Power kVA
kW kVA
cosphi 1.0 cosphi 0.8
10.3 INPUT CHARACTERISTICS
Module Range MX
Module Type DPA 30 S2 DPA 40 S2 DPA 50 S2
Output Rated Power per Module cosφ 0.8
kVA
30 40 50
Output Rated Power per Module cosφ 1.0
KW
24 32 40
Nominal Input Voltage V 3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input Voltage Tolerance
(ref to 3x400/230V) for Loads in %:
V
(-23%/+15%) 3x308/177 V to 3x460/264 V for <100 % load
(-30%/+15%) 3x280/161 V to 3x460/264 V for < 80 % load
(-40%/+15%) 3x240/138 V to 3x460/264 V for < 60 % load
Input Frequency Hz 30 - 70
Input Power Factor PF=0.99 @ 100 % load
Inrush Current A limited by soft start / max. In
Input Distortion THDI Sine-wave THDi = < 3 % @ 100% load
Max. Input Power with rated output power
and charged battery per Module
(output Cosφ = 1.0)
kW 25.5 34.0 42.6
Max. Input Current with rated output power
and charged battery per Module
(output Cosφ = 1.0)
A 36.8 49.1 62.1
Max. Input Power with rated output power
and discharged battery per Module
(output Cosφ = 1.0)
kW 28.1 37.4 46.8
Max. Input Current with rated output powe
and discharged battery per Module
(output Cosφ = 1.0)
A 40.7 54.2 67.8