EasyManua.ls Logo

ABB CONCEPTPOWER CLASSIC DPA-50 - Block Diagram Conceptpower Dpa; Single Feed Input (Standard Version)

ABB CONCEPTPOWER CLASSIC DPA-50
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202 Page 3/16 ABB
Printed in Switzerland – Modifications reserved
2.1.3 BLOCK DIAGRAM CONCEPTPOWER DPA
2.1.3.1 Single Feed input (Standard Version)
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Frame
type
Load
kVA
cosphi
0.8
Input 3x400V Output 3x400V cosphi 0.8 Battery
Fuse A
(Agl/CB)
Cable A (mm
2
)
(IEC 60950-1)
Max. Input
Current
with
battery
charging
(A)
Cable D (mm
2
)
(IEC 60950-1)
I nom
(A)
Fuse E
+ / N / -
(Agl/CB)
Cable E (mm
2
)
for CBAT DPA 120 or 200
ONLY
+ / N / -
Com. Battery Sep. Battery
MX Frames (Frames shall be cabled to there full rating capability)
CLASSIC
DPA 50
50 3x100A 5x25 67 5x25 72 A 3x100A*1 3x25 3x25
TRIPLE
DPA-150
150 3x250A 5x120 or 5x(2x50) 202 5x120 or 5x(2x50) 218 A 3x300A*1 3x150 3x (3x25)
UPGRADE
DPA-250
250 3x400A 5x(2x95) 337 5x(2x95) 362 A 3x500A*1 3x(2x150) 5x (3x25)
*1 only valid for common battery use
Cable D
Frame
Maintenance Bypass IA1
Load 3x400/230 V
UPS module 1
F1 F2
Static Switch
IA2-1
Inverter
Rectifier
UPS module 2..4
F1 F2
Static Switch
IA2-2..4
Inverter
Rectifier
UPS module 5
F1 F2
Static Switch
IA2-5
Inverter
Rectifier
Cable E
STANDARD VERSION (SINGLE FEED INPUT)
MAINS 3x400/230V
Cable A
Fuse A
Fuse E

Table of Contents