Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202 Page 8/16 ABB
Printed in Switzerland – Modifications reserved
14 15 16
1
2
3
4
5
6
7
8
9 10 11 12
14 15 16
19 20 21
13
1 X1-X4 Customer interface on Phoenix Terminals:
X1 Customer Inputs
X2…X4 = Potential free contacts (detail see Section 3 / 1.2 )
2 SW1-9 Multi-Cabinet Configuration Switch (see section 4)
3 JD8 Parallel BUS connector
ONLY For paralleling cabinets use optional adapter:
JD5 Parallel BUS - Input Connector
JD6 Parallel BUS - Output Connector
4 JD11 RS232 / Sub D9/ female, PC interface
5 JD12 RS232/ Sub D9 / male for Multidrop ONLY
6 USB PC Interface
7 SNMP Slot for optional SNMP card ONLY
8 Modem Slot for optional Modem/Ethernet card ONLY
9 9 Battery terminal + / N / - for separate bat. 16/25 mm2
9* 3 Battery terminal for common battery M10 + PE 1x M10
10 Input Bypass terminal for Dual Input feed 3xM10
11 Input Rectifier terminal for Single feed 4xM10
12 Output Load terminal 4xM10
13 IA1 Maintenance Bypass
14 IA2-1 Parallel Isolator UPS-Module 1
15 IA2-2 Parallel Isolator UPS-Module 2
16 IA2-3 Parallel Isolator UPS-Module 3
19 F4 Battery Fuse Holder Module 1 14x51/ 50A Fast Acting
20 F5 Battery Fuse Holder Module 2 14x51/ 50A Fast Acting
21 F5 Battery Fuse Holder Module 3 14x51/ 50A Fast Acting