04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 14/78 ABB
Modifications reserved
4 INSTALLATION AND WIRING
4.1 POSITIONING OF THE UPS AND BATTERY CABINET
The UPS is designed for location in a restricted access location only and should be located where:
The relative humidity does not exceed 95% (non-condensing) and the temperature remains always between
0°C and +40°C. Note: an optimal temperature for the UPS and especially for VRLA batteries is 20°C- 25°C.
The UPS room shall have temperature control (air-cooling)
Any kind of dust or corrosive/explosive gases must be absent
Fire protection standards are respected
The place is vibration free
The floor material should be non-flammable and strong enough to support the heavy load.
Cabling can be performed easily
Available front accessibility of 1m from front of the unit for service or maintenance
Only front access is necessary for service and maintenance
If the UPS will be installed in bayed enclosures, partition walls have to be installed as well
Also the needed clearances to allow proper airflow on the UPS system and to allow proper service and
maintenance shall be respected as reported in the Tables 5 and 6 here below.
Table 5: minimum clearances for single UPS
installation.
UPS Model
A
1
(mm)
B
1
(mm)
C
(°)
D
(mm)
DPA 500 300 1000 115° 400
Table 6: minimum clearances for UPS + other
cabinets in row.
UPS Model
A
2
(mm)
B
2
(mm)
C
(°)
D
(mm)
DPA 500 300 1000 115° 400
Figure 5: top view and indication of the Figure 6: Top view and indication of the minimum
minimum clearances for single UPS. clearances for UPS + other cabinets in row.
Accessibility Totally front accessibility for service and maintenance
Positioning Min. 30 cm rear space (required for fan)
Input and Output Power Cabling From the front bottom or top
B
1
A
1
UPS
Cabinet
door
opening
C
D top clearance
is only needed if
there is no side
clearance.
B
2
UPS
Cabinet
A
2
Battery cabinet
or other
equipment
Battery cabinet
or other
equipment
door
opening
C