04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 47/78 ABB
Modifications reserved
On the right hand side of the LCD there is a 3-digit indicator defining the UPS “Position” in the Multi-UPS system.
S stands for Single UPS. The system consists only of one UPS.
P01 stands for Parallel UPS in a Multi- UPS system and 01 stands for the first UPS (MASTER) in the
parallel UPS system.
P02 stands for Parallel UPS in a Multi- UPS system and 02 stands for the second UPS (SLAVE) in the
Multi- UPS system.
P03 stands for Parallel UPS in a Multi- UPS system and 03 stands for the third UPS (SLAVE) in the
Multi- UPS system.
The definition of the UPS “Position” in a parallel system is achieved in the Menu Set-Up Service.
DESCRIPTION LCD-DISPLAY
Single UPS Systems
SYSTEM CONFIGURATION
SINGLE
S
Parallel System e.g. first UPS cabinet
SYSTEM CONFIGURATION
PARALLEL
P01
Parallel System e.g. second UPS cabinet / Slave
LOAD OFF
SUPPLY FAILURE
P02
Note: The max no. of UPS units is 6.
6.5.7 Main Menu Screen
DESCRIPTION LCD-DISPLAY
1
Logging Control. A log of the last 99 events is stored in the
Power Management Display.
EVENT LOG
MEASUREMENTS
2
In Menu Measurements: monitor voltages, power,
frequencies, currents, autonomy etc.
MEASUREMENTS
COMMANDS
3
The Command Menu enables to perform the commands
“Load to inverter”, Load to bypass, battery test.
COMMANDS
UPS DATA
4
The UPS Data are the UPS personalized information
“serial number
UPS DATA
SET-UP USER
5
Various settings can be performed by the user: Date/Time,
automatic battery test, etc.
SET-UP USER
SET-UP SERVICE
6
Various adjustments can be performed by the service staff
SET-UP SERVICE
NO MORE MENU
6.5.8 Event Log Screen
DESCRIPTION LCD-DISPLAY
1
Logging Control; a log of the last 99 events is stored in the
Power Management Display.
01 05-10-08
LOCAL LOAD OFF
14:38:59
2
Every stored event is identified with a sequential number
and time stamp.
02 05-10-08
LOCAL LOAD TO BYP
14:38:56
3
By press ENTER the code of the event will be displayed. (Press
ENTER to come back to the previous indication)
03 8104
LOCAL LOAD TO INV
4
All events and alarms are indicated with their date and time
of appearance.
04 05-10-08
LOCAL LOAD TO INV
14:37:14