04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 38/78 ABB
Modifications reserved
Defining the UPS positioning in a system:
The position of each UPS within a system has to be configured not only in the graphical interface but also in the
hardware. The position is determined as one of the following:
• “First” UPS in the parallel configuration
• “Middle” UPS in the parallel configuration (there may be more than one)
• “Last” UPS in the parallel configuration. The maximum number of parallel cabinets is six (6). The maximum
number of parallel modules is thirty (30).
In a multi-cabinet configuration chain, the cabinet is seen as “First” and “Last” in an imaginary chain.
Configure the DIP switch for the existing system. For more details concerning the positions of this DIP switch, refer
to Chapter 6.2.3.
6.4.5 Mimic Diagram – system level
The mimic diagram is the default screen. It shows the power flow through the UPS system (single frame as well as
multi-cabinet configuration) and indicates its status. This diagram can be accessed from any screen using the
corresponding icon in the display header.
Figure 19: Mimic Diagram Screen - system level
The color of each block identify its functional status. There are four main colors in the mimic diagram:
• Green: In operation
• White: Inactive block
• Yellow: Warning condition
• Red: Fault condition