10.2 GENERAL CHARACTERISTICS
General characteristics - Frame Values Unit
Model: Conceptpower DPA 500
Power, rated:
apparent
500
kVA
active
500
kW
Power, range
100 - 3000
kW
UPS type: on-line, trasformerfree, modular, decentralized parallel architecture
Parallel capability: up to 6 frames
Battery: not included
Performance classification: VFI-SS-111
Mechanical
Dimensions (width × height × depth)
1580x1975x940
mm
Mass, approx. (500kW system, with 5 modules)
975
kg
Acoustic noise (acc. to IEC 62040-3)
in normal mode (at <=25°C) at 100% / 50% Load
75 / 67
dBA
in battery mode (at <=25°C) at 100% / 50% Load
73 / 66
Safety
Access: operator/restricted
Degree of protection against hazards and water ingress: IP 20
Electromagnetic compatibility
compliant
Emission UPS Cat / Immunity UPS Cat
C3 / C3
Environmental
Storage temperature range
-25 - +70
°C
Operative temperature range
0 - +40
°C
Relative humidity range (non-condensing)
≤ 95
%
Max. altitude without de-rating
1000
m
Additional and usual information
Connection: 5 wires, 3 phase + N + PE
Cable entry: top or bottom
Accessibility: frontal only
Color: Graphite Grey (RAL 7024)
Color code: Pulverlacke N°4222903402

Table of Contents

Other manuals for ABB Conceptpower DPA 500

Related product manuals