04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 46/78 ABB
Modifications reserved
6.5.3 ON/OFF Start-up and Shutdown Buttons
NOTE!
IN THE CASE THAT THE PARALLEL UPS SYSTEM HAS TO BE TURNED
OFF, THEN BOTH ON/OFF BUTTONS ON ALL UPS MODULES HAVE TO
BE PUSHED. IN THIS CASE THE POWER SUPPLY TO THE LOAD WILL
BE INTERRUPTED
6.5.4 Definition of a Single/Parallel-Module System
To define a single or parallel UPS the “SET-UP SERVICE” menu, which is password protected, need to be activat
ed using program line 4 “UPS MODEL”.
See Service Manual Section E.
6.5.5 Definition of a Single/ Multi-Cabinet Chain (DIP Switch SW1-6)
By means of the DIP Switch SW1-6, which is located on the front of a Cabinet, it is possible to determine the
“position” of the Cabinets in Multi-Cabinet Chain:
• “First” in the Multi-Cabinet Chain
• “Middle” in the Multi-Cabinet Chain (there may be more than one)
• “Last” in the Multi-Cabinet Chain.
NOTE: If a Cabinet is a Single Cabinet then it is seen as the “First” and “Last” in an imaginary Chain.
So the positions of the DIP Switch SW1-6 must be set as shown below:
Table 12: DIP Switch SW1-6
6.5.6 Status Screens
DESCRIPTION LCD-DISPLAY