04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 45/78 ABB
Modifications reserved
The 2 x 20 character LCD simplifies the communication with the UPS and provides the necessary monitoring
information about the UPS. The menu driven LCD enables the access to the:
• Even register (event log)
• Show measurements such as U, I, f, P, Q, S, load %, battery runtime and others
• Perform commands like start-up and shut-down of UPS and others
• Load transfer from INVERTER to BYPASS and vice-versa
• Diagnosis (SERVICE MODE)
• Adjustments and testing
6.5.1 LED Indicators
The mimic diagram serves to indicate the general status of the UPS. The LED-indicators show the power flow
status and in the event of mains failure or load transfer from inverter to bypass and vice-versa. The corresponding
LED-indicators will change colors from green (normal) to red (warning).
The LEDs LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply.
The LEDs INVERTER and BYPASS if green indicate which of the two is supplying power to the critical load. When
the battery is supplying the load due to mains failure the LED-indicator BATTERY is flashing.
The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time an
audible alarm will be activated.
INDICATOR INDICATOR STATUS MEANING
ALARM OFF
RED
No alarm condition
Alarm condition
LINE 1 GREEN
RED
Mains rectifier available
Mains rectifier not available
LINE 2 GREEN
RED
OFF
Mains bypass available
Main bypass not ok or not available
UPS is turned off
BYPASS GREEN
OFF
Load on bypass (Bypass-or Eco-Mode)
Bypass not operating (switched-off)
INVERTER GREEN
RED
OFF
Load on inverter
Inverter fault or load not transferable to inverter
Inverter not operating (switched-off)
BATTERY
GREEN
RED
Flashing RED
Flashing GREEN
Battery OK
Battery fault or battery is discharged
Battery in discharge and battery voltage critical or battery
fuse open
Battery in discharge and battery voltage good
6.5.2 Buttons
The buttons allow the user to operate the UPS to perform settings and adjustments, to start-up and shutdown the
UPS, to monitor on the LCD display the voltages, currents, frequencies and other values.