04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 70/78 ABB
Modifications reserved
10.3 INPUT CHARACTERISTICS
Input characteristics
UPS frame
values
UPS
module
values
Unit
Power, rated:
500
100
kW
Voltage (steady-state, r.m.s), rated:
3x380/220V+N
3x400/230V+N
3x415/240V+N
VAC
tolerance, refferred to 400/230V
-10 / +15 at <100% load
-20 / +15 at <80% load,
-30 / +15 at <60% load
%
Frequency, rated
50
Hz
tolerance, refferred to 50Hz
-30/+40
%
Current (r.m.s), rated (with battery charged and input 400/230V)
760
152
A
maximum (with battery charging and input 400/230V)
835
167
A
total harmonic distortion (THDi)
< 3.5
%
in-rush current
< 100% of rated current
%
Power factor
0.99 @ 100% load
Rated short-time withstand current (I
CW
)
25 for 1 s
-
kA, s
AC power distribution system: TN-S, TN-C, TN-C-S, TT
note: in static bypass mode or eco-mode TN-C and TN-C-S can cause PE current to rise above 5% of phase currents.
phases required
3
neutral required
yes
Additional and usual information
Connection: 5 wires, 3 phase + N + PE
Cable entry: top or bottom
Accessibility: frontal
Walk In/Soft Start: yes
Back feed protection: yes