04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx Page 77/78 ABB
Modifications reserved
10.8 OPTIONS
- Maintenance bypass
- SNMP cards
- Battery Cabinet
- Parallel KIT for paralleling multiple frames
- Wooden box
- Temp. sensor for battery temp. control
10.9 ON REQUEST
- INPUT / OUTPUT transformers for galvanic isolation or special voltages
- Bypass transformer
- IP 21
10.10 INSTALLATION PLANNING – UPS POSITIONING
Clearances needed to allow proper airflow on the UPS system and to allow door opening.
Minimum clearances for single UPS
UPS Model
A
1
(mm)
B
1
DPA 500 300 1000 115° 400
Minimum clearances for UPS + other cabinets in row
UPS Model
A
2
(mm)
B
2
DPA 500 300 1000 115° 400
Top view and indication of the minimum clearances for
single UPS.
Top view and indication of the minimum clearances for UPS +
other cabinets in row .
10.11 HEAT DISSIPATION
Module quantities 1 2 3 4 5
UPS power rating kW 100 200 300 400 500
Heat Dissipation with 100% linear load
W 4500 9000 13500 18000 22500
Heat Dissipation with 100% non-lin.load
(acc. to IEC 62040-3)
Airflow (25° - 30°C) with 100% non-lin. Load
(acc. to IEC 62040-3)
m
3
/h 1200 2400 3600 4800 6000
Heat Dissipation without load W 660 1320 1980 2640 3300
is only needed if
there is no side
clearance.
Battery cabinet
or other
equipment
Battery cabinet
or other
equipment