FOXCST REFERENCE
FOX61xLEDE1 33
“Main - Inventory”,
“Main - Logbooks”, and
“Main - Software”
management functions description, please refer to "1KHW002466 FOXCST
Operation".
8.2.3 AP: / unit-x, Fault Management
For the a description of the general aspects of the
“Fault Management - Status”, and
“Fault Management - Configuration”
management functions, please refer to "1KHW002466 FOXCST Operation".
The following table lists the fault causes of the current AP.
Table 8: AP: / unit-x, Fault Management
ID Fault Cause Event Type Traffic
Affecting
Default
Severity
Description
SWM Software Mismatch Equipment
Alarm
Minor The running ESW does not match the
assigned ESW.
SSWNA Scheduled Software
Not Available
Equipment
Alarm
Minor The ESW that is scheduled for installa-
tion is not available on the unit. Make
sure that the ESW is downloaded to the
unit.
SWIN Software Incompatible
With Network Element
Equipment
Alarm
Major The running ESW is not compatible with
the version required by the NE type or
version.
PRC PBUS Resource Con-
flict
Processing
Error Alarm
Major The PBUS access circuit of another TDM
unit in the subrack is defective.
Remove or unassign the other TDM units
in the subrack one by one until the alarm
is cleared. Replace the defective unit.
EQM Equipment Malfunction Equipment
Alarm
Critical The LEDE1 controller detects any anom-
alies on the unit, e.g. a voltage is miss-
ing, a chip does not respond, etc.
HWIC Hardware Incompatible
With Configuration
Equipment
Alarm
Major The plugged HW is not compatible with
the unit configuration HW stored in the
database. You may need to change the
HW or re-create the configuration for the
unit.
SWIC Software Incompatible
With Configuration
Equipment
Alarm
Major The ESW running on the unit is not com-
patible with the unit configuration stored
in the database. You may need to
upgrade, or downgrade the ESW, or re-
create the configuration with the cur-
rently running ESW.
GSW General Software
Alarm
Equipment
Alarm
Major An ESW internal error has been detected
that might inhibit the ESW from running
correctly.
MFA Maintenance Function
Active
Communica-
tion Alarm
Warning A maintenance function has been acti-
vated by the operator.
UNAV Unit Not Available Equipment
Alarm
Critical The unit that is configured is either not
plugged or not recognized due to a fail-
ure.