V
ref
I
dir
ANSI09000636-1-en.vsd
1
2
2
3
4
ANSI09000636 V1 EN
Figure 35: Directional function characteristic
1. RCA = Relay characteristic angle 55°
2. ROA = Relay operating angle 80°
3. Reverse
4. Forward
6.2.3.1 Settings for steps 1 to 4
n means step 1 and 4. x means step 1, 2, 3 and 4.
DirModeSelx: The directional mode of step x. Possible settings are Disabled/Non-
directional/Forward/Reverse.
Section 6 1MRK 511 286-UUS A
Current protection
94
Application manual