EasyManua.ls Logo

ABB REC650 - Summation Block 3 Phase 3 PHSUM

ABB REC650
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Assume instance SMAI_20_7:1 in task time group 1 has been selected in the
configuration to control the frequency tracking (For the SMAI_20_x of task time group
1). Observe that the selected reference instance (i.e. frequency tracking master) must be
a voltage type. Observe that positive sequence voltage is used for the frequency tracking
feature.
For task time group 1 this gives the following settings (see Figure
149 for numbering):
SMAI_20_1:1 DFTRefExtOut = DFTRefGrp7 to route SMAI_20_7:1 reference to the
SPFCOUT output, DFTReference = DFTRefGrp7 for SMAI_20_7:1 to use
SMAI_20_7:1 as reference (see Figure
150). .
SMAI_20_2:1 - SMAI_20_12:1 DFTReference = DFTRefGrp7 for SMAI_20_2:1 -
SMAI_20_12:1 to use SMAI_20_7:1 as reference.
For task time group 2 this gives the following settings:
SMAI_20_2:2: DFTReference = ExternalDFTRef to use DFTSPFC input as reference
(SMAI_20_7:1); DFTRefExtOut = ExternalDFTRef (even if the output SPCFOUT is not
wired in AC).
SMAI_20_2:2 - SMAI_20_12:2 DFTReference = ExternalDFTRef to use DFTSPFC
input as reference (SMAI_20_7:1)
15.10 Summation block 3 phase 3PHSUM
15.10.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Summation block 3 phase 3PHSUM - -
15.10.2 Application
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of three-
phase analog signals (of the same type) for those IED functions that might need it.
15.10.3 Setting guidelines
The summation block receives the three-phase signals from SMAI blocks. The
summation block has several settings.
Section 15 1MRK 511 286-UUS A
Basic IED functions
338
Application manual

Table of Contents

Other manuals for ABB REC650

Related product manuals