EasyManua.ls Logo

ABB REC650 - Nd Harmonic Restrain

ABB REC650
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
protection. The maximum ground-fault current at the local source can be used to calculate
the value of ZN as V/(√3 · 3I
0
) Typically, the minimum ZNPol (3 · zero sequence source)
is set. Setting is in primary ohms.
When the dual polarizing method is used it is important that the product INx>· ZNpol is
not greater than 3V
0
. If so, there is a risk for incorrect operation for faults in the reverse
direction.
IPolMin: is the minimum ground-fault current accepted for directional evaluation. For
smaller currents than this value the operation will be blocked. Typical setting is 5-10% of
IBase.
VPolMin: Minimum polarization (reference) residual voltage for the directional function,
given in % of VBase/√3.
IDirPU: Operate residual current release level in % of IBase for directional comparison
scheme. The setting is given in % of IBase and must be set below the lowest INx> setting,
set for the directional measurement. The output signals, PUFW and PUREV can be used
in a teleprotection scheme. The appropriate signal should be configured to the
communication scheme block.
6.4.3.3 2nd harmonic restrain
If a power transformer is energized there is a risk that the current transformer core will
saturate during part of the period, resulting in a transformer inrush current. This will give
a declining residual current in the network, as the inrush current is deviating between the
phases. There is a risk that the residual overcurrent function will give an unwanted trip.
The inrush current has a relatively large ratio of 2nd harmonic component. This
component can be used to create a restrain signal to prevent this unwanted function.
At current transformer saturation a false residual current can be measured by the
protection. Also here the 2
nd
harmonic restrain can prevent unwanted operation.
2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2nd
harmonic restrain signal. The setting is given in % of the fundamental frequency residual
current.
HarmRestrainx: Enable block of step x from the harmonic restrain function.
6.4.3.4 Line application example1
The Four step residual overcurrent protection EF4PTOC (51N/67N) can be used in
different ways. Below is described one application possibility to be used in meshed and
effectively grounded systems.
Section 6 1MRK 511 286-UUS A
Current protection
112
Application manual

Table of Contents

Other manuals for ABB REC650

Related product manuals